Silicon Cables - Silimul-B 7.2kV
High Temperature Medium Voltage Cable
Silicon Insulated and Braided Cable
SILIMUL-B 1.1 kV , -60 to 180oC
CHARACTERISTICS
General
- Continious operating temperature -60 to 180oC
- Good resistance to thermal shock and UV
- Excellent mechanical strength
- Standard Colour : Grey , White
Electrical
- Rated voltage : 6.6/7.2 kV
- Test Voltage : 15 kV
Marking : RAVIRAJ {cross section} 7200V [] Mtr
Flexible tin plated copper conductor , Class 5 as per IEC60228
Semiconducting tape
Silicon insulation
Coated synthetic braid
Standards & Approvals
- IEC 60228
- IEC 61034-2
- IEC 60332-1-2
- IEC 60754-1
- IEC 61034-1
- IEC 60754-2
Other Options
- Extra-flexible tin-plated copper core - class 6 as per IEC60228 : Contact us.
- Flexible or extra-flexible bare copper, silver-plated or nickel-plated copper - class 5 or 6 as per IEC60228 : Contact us.
- Multi core cable made up of SILIMUL-B : Contact us.
- Other markings: Contact us.
- Other colours: Contact us.
- Other nominal cross-sections: Contact us.
- Other options and/or combinations of the options outlined above: Contact us.
Application
- Cabling for rotating machine : Motor , Generator , Alternator
- Cabling for static machine : Transformer, Inductor, Inverter, Chopper
- Ship building & railway construction
- Power cabinet
Size |
Cond. OD (Nom) |
Max. Resistnace @ 200C | Insu. Thick (Nom.) | Outer Dia.* (Nom.) | Approx. Wt/km | |
Bare Cu | Tinned Cu | |||||
[mm2] | [mm] | [Ω/km] | [mm] | [mm] | [mm] | |
1.5 | 1.6 | 13.3 | 13.7 | 2.40 | 7.4 | |
2.5 | 2.1 | 7.98 | 8.21 | 2.40 | 7.9 | |
4 | 2.6 | 4.95 | 5.09 | 2.40 | 8.4 | |
6 | 3.2 | 3.3 | 3.39 | 2.40 | 9.0 | |
10 | 4.0 | 1.91 | 1.95 | 2.40 | 9.8 | |
16 | 5.1 | 1.21 | 1.24 | 2.40 | 10.9 | |
25 | 6.2 | 0.780 | 0.795 | 2.80 | 12.8 | |
35 | 7.7 | 0.550 | 0.565 | 2.80 | 14.3 | |
50 | 9.2 | 0.390 | 0.393 | 2.80 | 15.8 | |
70 | 10.8 | 0.270 | 0.277 | 2.80 | 17.4 | |
95 | 12.5 | 0.210 | 0.210 | 2.80 | 19.1 | |
120 | 16.0 | 0.161 | 0.164 | 2.80 | 22.6 | |
150 | 17.2 | 0.129 | 0.132 | 2.80 | 23.8 |