Silicon Cables - Silimul-C 4.2kV
High Temperature Medium Voltage Cable
Silicon Insulated and Sheathed Cable
SILIMUL-C 1.1 kV , -60 to 180oC
CHARACTERISTICS
General
- Continious operating temperature -60 to 180oC
- Good resistance to thermal shock and UV
- Excellent mechanical strength
- Standard Colour : Red , White
Electrical
- Rated voltage : 3.8/4.8 kV
- Test Voltage : 10 kV
Marking : RAVIRAJ {cross section} 4200V [] Mtr
Flexible tin plated copper conductor , Class 5 as per IEC60228
Optional seperating tape
Silicon insulation
Outer Sheath - Silicon
Standards & Approvals
- IEC 60228
- IEC 61034-2
- IEC 60332-1-2
- IEC 60754-1
- IEC 61034-1
- IEC 60754-2
Other Options
- Extra-flexible tin-plated copper core - class 6 as per IEC60228 : Contact us.
- Flexible or extra-flexible bare copper, silver-plated or nickel-plated copper - class 5 or 6 as per IEC60228 : Contact us.
- Multi core cable made up of SILIMUL-C : Contact us.
- Other markings: Contact us.
- Other colours: Contact us.
- Other nominal cross-sections: Contact us.
- Other options and/or combinations of the options outlined above: Contact us.
Application
- Cabling for rotating machine : Motor , Generator , Alternator
- Cabling for static machine : Transformer, Inductor, Inverter, Chopper
- Ship building & railway construction
- Power cabinet
Size |
Cond. OD (Nom) |
Max. Resistnace @ 20oC | Insu. Thick (Nom.) | Outer Dia.* (Nom.) | Approx. Wt/km | |
Bare Cu | Tinned Cu | |||||
[mm2] | [mm] | [Ω/km] | [mm] | [mm] | [mm] | |
1.5 | 1.6 | 13.3 | 13.7 | 1.87 | 5.3 | |
2.5 | 2.1 | 7.98 | 8.21 | 1.87 | 5.8 | |
4 | 2.6 | 4.95 | 5.09 | 1.87 | 6.3 | |
6 | 3.2 | 3.3 | 3.39 | 1.87 | 6.9 | |
10 | 4.0 | 1.91 | 1.95 | 1.87 | 7.7 | |
16 | 5.1 | 1.21 | 1.24 | 1.87 | 8.8 | |
25 | 6.2 | 0.780 | 0.795 | 1.87 | 9.9 | |
35 | 7.7 | 0.550 | 0.565 | 1.87 | 11.4 | |
50 | 9.2 | 0.390 | 0.393 | 1.87 | 12.9 | |
70 | 10.8 | 0.270 | 0.277 | 1.87 | 14.5 | |
95 | 12.5 | 0.210 | 0.210 | 2.67 | 17.8 | |
120 | 16.0 | 0.161 | 0.164 | 2.67 | 21.3 | |
150 | 17.2 | 0.129 | 0.132 | 2.67 | 22.5 |
* The diameter is provided for information purposes as it may vary depending on the stranding of the core. Only the average thickness of insulation should be taken into account.